General Details
temperature range | -30 °C… +70 °C |
Bending radius min. | 10 x D |
Loop resistance | Ø 0,80mm max. 73,2 Ω/km Ø 1,0 mm max. 44,4 Ω/km 1,0 mm2 max. 36,2 Ω/km 1,5 mm2 max. 24,2 Ω/km 2,5 mm2 max. 14,8 Ω/km |
Insulation resistance min. | 100MΩx km |
Capacitance max. | 120nF/km |
capacitance imbalance max. | 200pF/100 m |
Test voltage | 500 Vac damar/damar 2000 Vac damar/ekran |
Operating voltage max. | 225 V |
Standards | TSE K 173, DIN VDE 0815 |
fire performance | Vertical flame spread EN 60332-1-2 Corrosive gas EN 60754-1/2Smoke density EN 61034-2Current continuity IEC 60331-21 FE180Current continuity EN 50200 PH120 |
EU declaration of conformity | LVD Low Voltage Regulation 2014/35/EU RoHS Restriction of Use of Certain Hazardous Substances 2011/65/EU |
Usage areas
It is used in the fire alarm system, control and supply of the devices that need to work during the fire. It is used in systems that need to maintain its function for a certain period of time (current continuity FE180 mechanical shock current continuity PH120), such as the operation of devices and equipment required for emergency lighting, monitoring and evacuation, and warning systems. The cable, which has a static screen, is protected against external signals. Smart or semi-intelligent buildings, mass housing, hospitals, cinemas, theaters, where people are concentrated, especially in places that should not be affected by fire conditions, since halogen-free material is used in the cable structure. , schools, shopping malls, airports, factories etc. used in buildings.
Cable Structure
Conductive | electrolytic copper wire |
İzolasyon | Halogen-free, cross-linked insulation, in accordance with DIN VDE 0815 insulation color coding, EI8 EN 50363-5 |
Ayırıcı bant | Pet tape min. 100% coverage Glass fiber tape min.100% coverage |
Ekran | Tinned copper wire mesh Al-Pet tape min. 100% coverage |
Sheath | HFFR, RAL 2003 Orange 70°C EN 50290-2-27 HM2 DIN VDE 0207-24 |