27.09.2021
722
LIHH

General Details

temperature range-30 °C… +70 °C
Bending  radius min.10 x D
Conductor resistance0,75 mm2 max. 26,0 Ω/km
1,0 mm2 max. 19,5 Ω/km
1,5 mm2 max. 13,3 Ω/km
2,5 mm2 max. 7,98 Ω/km
Insulation resistance min.20MΩx km
Test voltage0,75 mm2 1200 V
1,0 mm2 1200 V
1,5 mm2 2500 V
2,5 mm2 2500 V
Operating voltage max.300 V
StandardsTSE K 178, DIN VDE 0812
fire performanceVertical flame spread EN 60332-1-2 Corrosive gas EN 60754-1/2Smoke density EN 61034-2Current continuity IEC 60331-21 FE180Current continuity EN 50200 PH120
EU declaration of conformityLVD Low Voltage Regulation 2014/35/EU RoHS Restriction of Use of Certain Hazardous Substances 2011/65/EU

Usage areas

It is used in the control and supply of devices that need to work during a fire. It is used in systems that need to maintain its function for a certain period of time (current continuity FE180 mechanical shock current continuity PH120), such as the operation of devices and equipment required for emergency lighting, monitoring and evacuation, and warning systems. Smart or semi-intelligent buildings, mass housing, hospitals, cinemas, theaters, where people are concentrated, especially in places that should not be affected by fire conditions, since halogen-free material is used in the cable structure. , schools, shopping malls, airports, factories etc. used in buildings.

If requested, the following types with number code can be produced. LIHH-OZ: cores black, white number coded

Cable Structure

ConductiveStranded copper wire, Class 5, IEC 60228
InsulationHalogen-free, cross-linked insulation, in accordance with DIN 47100 insulation color coding, EI8 EN 50363-5
separator tapePet tape min. 100% coverage Glass fiber tape min.100% coverage
SheathHFFR, RAL 2003 Orange 70°C EN 50290-2-27 HM2 DIN VDE 0207-24