General Details

temperature rangeconstant:-30 °C… +70 °C
active: 0 °C… +50 °C
Bending radius min.constant min. : 7,5 x D
active min. : 15 x D
Conductor resistance0,22 mm2 max. 96,0 Ω/km
0,50 mm2 max. 39,0 Ω/km
0,75 mm2 max. 26,0 Ω/km
1,0 mm2 max. 19,5 Ω/km
1,5 mm2 max. 13,2 Ω/km
2,5 mm2 max. 7,98 Ω/km
Insulation resistance min.200MΩx km
Test voltage0,22 mm2 1200 V
0,50 mm2 1200 V
0,75 mm2 1200 V
1,0 mm2 1200 V
1,5 mm2 2500 V
2,5 mm2 2500 V
Operating voltage max.300 V
StandardsTSE K 353, DIN VDE 0812
fire performanceVertical flame spread EN 60332-1-2 Corrosive gas EN 60754-1/2 Smoke density EN 61034-2
EU declaration of conformityLVD Low Voltage Regulation 2014/35/EU RoHS Restriction of Use of Certain Hazardous Substances 2011/65/EU

Usage areas                

Halogen Free insulated and sheathed cable is used as signal transmission cable in indoor environments. Thanks to its flexible and thin structures, it provides advantages in narrow space applications. It is used in industrial electronics, computer and office machines, indoor communication, sound and security systems. The cable, which has a braided screen, is protected against electromagnetic interference from the environment. Since halogen-free material is used in the cable structure (it does not take the flame late and does not transmit it, does not emit toxic gas after combustion and does not create black smoke that blocks vision), it is used in buildings where people are concentrated, especially in places that should not be affected by fire conditions.

If requested, the following types with number code can be produced.

LIHCH-OZ: cores black and white number coded

LIHCH-JZ: with earth protection core (yellow/green), cores black and white number coded

Cable Structure

ConductiveStranded copper wire Class 5, IEC 60228
InsulationHFFR, according to DIN 47100 insulation color coding 70°C EN 50290-2-26, HJ2 DIN VDE 0207-23
separator tapePet tape min. 100% coverage
ScreenTinned copper wire mesh
SheathHFFR, RAL 7001 Gray 70°C EN 50290-2-27, HM2 DIN VDE 0207-24